Ferraz Shawmut Tri-OnicĀ® Time Delay Fuse, Current Limiting Low Voltage, Series: TRS-R, Non-Indicating, Rejection, 15 A, 600 VAC/300 VDC, 200/20 kA Interrupt, Class: RK5, Ferrule Terminal, Clip Mount, Cylindrical Body, Dual Element, Polyester, 13/16 in Dia x 2 in L Body Size
Mersen (Ferraz Shawmut) TRS Series low voltage class RK5 current limiting time delay fuse. With advanced material technology added to the existing product, the TR current-limiting time-delay fuses are engineered for overcurrent protection of motors and transformers, service entrance equipment, feeder and branch circuits. Tri-Onic®Fuse's proven time-delay characteristic safely handles harmless starting currents and inrush currents associated with today's motors and transformers.TRS Class RK5 600V AC Time-Delay
Agency Information:UL Listed to Standard 248-12 File E2137. CSA Certified to Standard C22.2 No. 248.12
- DC Listed to UL Standard 248
Features and Benefits
- Time Delay: for motor start-ups and transformer inrush currents without nuisance opening
- Current Limiting: for low peak let through current
- Rejection-Style Design: prevents replacement errors (when used in recommended fuse blocks)
- Easy-To-Read-Label: for quick recognition and replacement
- Metal-Embossed Date and Catalog Number: for traceability and lasting identification
- Fiberglass Body: provides dimensional stability in harsh industrial settings
- High-Grade: silica filler ensures fast arc quenching and high current limitation
Applications
- Motor Circuits
- Mains
- Feeders
- Branch Circuits
- Transformers
- Service Entrance Equipment
- General-Purpose Protection
-
Manufacturer: Mersen
-
Brand: Ferraz Shawmut
-
PN: TRS15R
-
CX SKU: 798004
-
UPC: 782001748821
- Type: Time Delay Class RK5 Fuse
- Series: TRS-R
- Class: RK5
- Amperage Rating: 15 A
- Voltage Rating: 600 VAC/300 VDC
- Rejection/Non-Rejection: Rejection
- Interrupt Rating: 200/20kA
- Terminal Type : Ferrule
- Body Style : Cylindrical
- Element : Dual
- Material : Polyester
- Body Size : 13/16 in Dia x 5 in L
|